California Fire Code Exit Requirements:
A Guide to the 2025 CFC
California fire code exit requirements decide how people get out of a building in an emergency: how many exits it needs, how wide the doors and corridors are, how exits are marked, and how they stay lit when the power fails. Most of the rules match the International Fire Code, but California adds a few of its own, like low-level exit signs.
Key takeaways
- California uses the 2025 California Fire Code (Title 24, Part 9) from January 1, 2026.
- Exit doors need 32 inches of clear width and 80 inches of height, and must open without a key.
- Exit signs must stay lit at least 90 minutes after a power loss.
- California adds low-level exit signs in corridors of Group A, E, I, and R-2.1 buildings.
- Emergency lighting must average 1 footcandle for at least 90 minutes.
This guide covers the main requirements building owners, managers, and fire protection contractors need to know.
Which Code Applies in California?
The 2025 California Fire Code (Title 24, Part 9) took effect on January 1, 2026. It's based on the 2024 International Fire Code with California amendments. Exit rules in the fire code match Chapter 10 of the California Building Code.
City and county fire departments can adopt stricter local amendments, so always check with your local fire marshal (the authority having jurisdiction, or AHJ). California amendments apply to buildings permitted on or after January 1, 1989.
California Exit Requirements at a Glance
| Requirement | 2025 CFC / CBC rule |
|---|---|
| Exit door width | 32 in minimum clear opening (§1010.1.1) |
| Exit door height | 80 in minimum clear height (§1010.1.1) |
| Door hardware height | 34 to 48 in above the floor (§1010.2.3) |
| Opening | From the egress side, without a key or special knowledge (§1010.2) |
| Unlatching | One motion releases all locks and latches (§1010.2.1) |
| Door swing | Outward, in the direction of travel, for rooms with 50 or more people |
| Number of exits | 2 for up to 500 people, 3 for 501 to 1,000, 4 for more than 1,000 |
| Corridor width | Generally 44 in; 36 in when serving fewer than 50 people |
| Exit sign spacing | No more than 100 ft apart, or the sign's listed viewing distance (§1013.1) |
| Exit sign power | Lit at all times, at least 90 minutes on backup (§1013.6.3) |
| Emergency lighting | Average 1 footcandle, minimum 0.1, for at least 90 minutes (§1008.3) |
Exit doors
Exit doors must open easily from the inside without a key, tool or special effort. Deadbolts that need a key are only allowed in limited cases, such as the main entrance of some stores and offices with a sign that reads "This door to remain unlocked when the building is occupied." Rooms that hold 50 or more people need doors that swing out, and assembly and school spaces of that size usually need panic hardware.
Exit width and number of exits
The required width of stairs, corridors and doors depends on the occupant load. The building code sets a width per person for stairways and a smaller one for other exit parts, and some uses (schools, hospitals) need wider corridors. Your architect or the AHJ will confirm the numbers for your building.
Keep the path clear
The exit route has to stay clear all the way to the street. No storage in corridors, no blocked stairwells and no locked gates in the path while the building is occupied.
Where California Differs From the IFC
Low-level exit signs
This is the big California-only rule. Under CFC §1013.7, interior corridors in Group A (assembly), E (schools), I (institutional) and R-2.1 (licensed residential care) buildings need low-level exit signs in addition to the regular ones above the doors. The bottom of the sign sits 6 to 8 inches above the floor, so people crawling under smoke can still find the way out.
Some Group I and R-2.1 buildings with smoke barriers, and Group I-3 (jails), have exceptions.
Exit sign illumination
Exit signs must be internally or externally lit and stay lit at all times. On backup power, they need to run at least 90 minutes. In hospitals (Group I-2), signs can't rely on unit batteries alone. Tactile exit signs at doors for people with low vision don't need to be lit.
Emergency lighting
When normal power fails, exit paths must have emergency lighting that averages 1 footcandle at floor level, with no spot below 0.1 footcandle, for at least 90 minutes.
Workplace rules
Employers also have to meet Cal/OSHA's exit rules in Title 8, §3235, which cover keeping exits marked, unlocked and clear for employees.
Common Exit Violations in California
Fire inspectors see the same problems again and again:
- Exit signs that are dark, damaged or have dead backup batteries
- Emergency lights that fail the 90-minute test
- Missing low-level exit signs in schools, care facilities and assembly spaces
- Exit doors that are locked, chained or need a key from the inside
- Storage, carts or furniture blocking corridors and stairwells
- Doors that swing the wrong way or don't close and latch
Most of these are easy to catch with a monthly walk-through and a yearly test.
For Fire Protection Contractors
Exit signs and emergency lights need a quick check every month and a full 90-minute test once a year, and California inspectors expect records of both. Tracking that by hand across dozens of buildings is where things slip.
ZenFire helps fire contractors stay on top of it:
- Recurring inspections: schedule monthly and annual exit sign and emergency light tests so none get missed.
- Compliance-ready forms: techs fill out inspection reports on a phone, with photos of each failed device.
- Quote before you leave: turn failed lights and missing signs into a quote on site.
Frequently asked questions
What fire code does California use in 2026?
The 2025 California Fire Code (Title 24, Part 9), in effect since January 1, 2026. It's based on the 2024 International Fire Code with California amendments.
How wide does an exit door need to be in California?
At least 32 inches of clear opening and 80 inches tall. Larger rooms may need more door width based on the number of people.
Does California require low-level exit signs?
Yes, in interior corridors of Group A, E, I, and R-2.1 buildings, with the bottom of the sign 6 to 8 inches above the floor. Some exceptions apply.
How long must exit signs stay lit on backup power?
At least 90 minutes after normal power is lost.
How many exits does a building need in California?
Two exits for up to 500 people, three for 501 to 1,000, and four for more than 1,000. Some small spaces can have one exit.
Can exit doors be locked in California?
Not from the inside while the building is occupied. They must open without a key or special effort, with a few limited exceptions.




